250 Lt Exp Vessel 6 bar Ø634x890 High Vert

Expansion vessel for accomodating the thermal expansion of sealed heating systems. Model EVCP is rated at 4, 5 or 6 bar depending on size and approved for primary circuit unvented heating applications. These systems normally feature a pressuristaion unit such as the Arrow Valves Autofill. For wholesome water or heating applications where 10 bar rating is required, refer to model EVUP.
Product Code: EVCP250
Postcode

Availability: In stock

£350.00

Additional Information

Heating - Size 250L
Heating - Powered No
Heating - Backflow Prevention No

Application

Unvented Heating Systems; Commercial (non drinking).

Downloads & Resources

Specification Clauses

The primary heating system expansion shall be accommodated in an air charged Expansion Vessel - model EVCP - as distributed by Arrow Valves Ltd – Tel 01442 823123 www.arrowvalves.co.uk. The vessel body shall be mild steel with red epoxy coating with a bottom entry male connection. The butyl membrane shall be suitable for 99 degrees Celsius at 6 bar (for 80 litres and larger). A separate expansion vessel ball valve with wire lock, drain tap and union – model BVEV – shall be supplied to enable draining of the vessel in order to periodically check the air charge. The vessel must be correctly sized. The pre-charge pressure shall be 0.2 bar less than the switch on pressure of a booster pump.