“Boost-A-Break” - Break Tank & Booster Set
Part Number: BTAB (was BTABV)



• Features & Benefits • Service Sheets / Manuals

• Approval Certificate

 

Product Overview
BTAB 700 / 900 /1200 / 4-2 / 4-3 / 4-4

Break Tank assembly with Fluid Category 5 protection by virtue of the integral Type AB air gap. The unit is supplied as a complete package on a base plate ready for installation.

The primary purpose is to provide backflow protection in accordance with the new Water Regulations. The BTAB unit also boosts the water pressure for elevated areas or where a high flow rate is required – e.g. wash-down.

The relatively large 24 litre pressure vessel allows about 5 litres of water to be supplied without switching the pump on. There is a choice of six pump sizes – 700 W, 900 W, 1200 W, 4-2, 4-3 & 4-4. The pump starts automatically when the pressure drops to that selected on the adjustable pressure switch.

The cistern has a screened overflow and weir, making it suitable for unorthodox drinking (wholesome) water applications, which require a “Hygienic type AB air gap” – e.g. dental spittoons & food preparation (G16.13 – was Byelaw 30).
The unit is compact by virtue of the small 18 litre cistern. Care should be taken not to empty the cistern by ensuring the output flow is not greater than the inlet – see datasheet table.

Fast filling is achieved by a servo-controlled solenoid valve with solid-state level probe control. This system has proved to be more reliable and accurate than conventional float valves.

The unit is quiet by virtue of a centrifugal pump, anti-vibration rubber feet and flexible stainless braided connection hoses.

For domestic boosting use "Pent-A-Boost" - model BTAF

For higher flow rates and variable speed pumps see variable speed "Boost-A-Break" - model BTAB 3-5 / 3-7 / 3-10 / 5-4 / 5-8 / 5-10 / 5-16 - Similar to fixed speed "Boost-A-Break" but with variable speed inverter pump and a very fast filling stainless steel cistern. BMS outputs. Pump duties up to a remarkable 2 Lt/s output.

For dual pumps see dual pump "Boost-A-Break" - model BTAB 3-7S / 3-10S / 5-4S / 5-8S / 3-7A / 3-10A -
Available as Duty Standby (one pump runs at a time) or Duty Assist (allows the second pump to switch on as required - doubling output). Both pumps are variable speed. The footprint is the same as the single pump yet the duty is up to 2.4 Lt/s output.

Associated Products:

• Brackets (BTBRA) (up to 5-8)
• Drip Tray (BTDT1/BTDT2) - GRP drip tray c/w float switch (up to 3-7). Model BTDT2 includes controller and additional solenoid
• Enclosure (BTCAB1/BTCAB2) - Outdoor GRP enclosure incorporating heater and thermostat. BTCAB1 features a large door, whereas BTCAB2 is compact and has a lift-off cover
• Wall Cover (BTCAB3) - Brackets required - see above. Heater and thermostat optional
• Washdown Guns - Medium Duty and Heavy Duty
• Pressure Regulating Valve PRV536

 

Specification Clause

Fixed Speed Pump
A Break Tank and Booster set with a hygienic Type AB air gap “Boost-A-Break” shall be installed – model BTAB9001 - as manufactured and distributed by Arrow Valves Ltd - Tel 01442 823123 www.arrowvalves.co.uk. The unit shall have an 18 litre cistern, with a lid, screened weirs, cistern drip tray requiring a DN40 overflow. The pump shall be centrifugal with stainless steel impellors and housing with an input power of 2.7 bar @ 1 Lt/s and a closed valve head of 4.52 and be controlled by a pressure switch connected to a 24 litre pressure vessel. The cistern level shall be controlled automatically by a servo solenoid valve operated via stainless steel conductive electrodes and controller. A low-level pump cut-out shall be controlled by electrodes in the cistern, which shall automatically reset once the cistern is sufficiently full. The cistern shall feature a high-level alarm linked to a volt free BMS relay - model BTBMS1. The unit shall feature a stainless steel base plate and be acoustically attenuated with anti-vibration feet and stainless steel braided flexible hoses. A 22 mm3 supply is required, which must maintain a dynamic pressure of 1.2 bar4.

Amend as required:
[1] 700 or 900 or 1200 or 4-2 or 4-3 or 4-4
[2] 1.9 bar @ 1 Lt/s and a closed valve head of 3.3 bar (model 700)
[2] 3.3 bar @ 1 Lt/s and a closed valve head of 5.7 bar (model 1200)
[2] 1.8 bar @ 1 Lt/s and a closed valve head of 2.4 bar (model 4-2)
[2] 2.7 bar @ 1 Lt/s and a closed valve head of 3.4 bar (model 4-3)
[2] 3.6 bar @ 1 Lt/s and a closed valve head of 4.5 bar (model 4-4)
[3] 28 mm (standard on model 1200, optional on others)
[4] 1.0 bar (where 28 mm supply specified)

Variable Speed Pump up to 1.2 lt/s
A Break Tank and Booster set with a hygienic Type AB air gap “Boost-A-Break” shall be installed – model BTAB3-71 - as manufactured and distributed by Arrow Valves Ltd - Tel 01442 823123 www.arrowvalves.co.uk. The unit shall have an 18 litre cistern, with a lid, screened weirs, cistern drip tray requiring a DN40 overflow. The pump shall be centrifugal with stainless steel impellors and housing. The pump speed shall be varied by an integral inverter to provide a constant pressure. The duty at 100% output shall be 3.0 bar2 @ 0.9 lt/s and be controlled by a pressure transducer, which is damped with a 24 litre pressure vessel. The cistern level shall be controlled automatically by a servo solenoid valve operated via stainless steel conductive electrodes and controller. A low-level pump cut-out shall be controlled by electrodes in the cistern, which shall automatically reset once the cistern is sufficiently full. The cistern shall feature a high-level alarm linked to a volt free BMS relay - model BTBMS2. The unit shall feature a stainless steel base plate and be acoustically attenuated by anti-vibration feet and stainless steel braided flexible hoses. A 28 mm3 supply is required, which must maintain a dynamic pressure of 1.0 bar4.

Amend as required:
[1] 3-5
[2] 1.8 bar (model 3-5)
[3] 22 mm (for model 3-5)
[4] 1.2 bar (required for model 3-5 with 22 mm inlet)

Variable Speed Pump up to 2.0 lt/s
A Break Tank and Booster set with a hygienic Type AB air gap “Boost-A-Break” shall be installed – model BTAB5-81 - as manufactured and distributed by Arrow Valves Ltd - Tel 01442 823123 www.arrowvalves.co.uk. The unit shall have a 24 litre nominal cistern and stainless steel raised valve chamber, with a lid, screened weirs, cistern drip tray with two DN40 connections, which require an overflow pipe. The pump shall be centrifugal with stainless steel impellors and housing. The pump speed shall be varied by an integral inverter to provide a constant pressure. The duty at 100% output shall be 3.0 bar @ 2 lt/s2 and be controlled by a pressure transducer, which is damped with a 24 litre pressure vessel. The cistern level shall be controlled automatically by two servo solenoid valves operated via stainless steel conductive electrodes and controller. A low-level pump cut-out shall be controlled by electrodes in the cistern, which shall automatically reset once the cistern is sufficiently full. The cistern shall feature a high-level alarm linked to a volt free BMS relay - model BTBMS2. The unit shall feature a stainless steel base plate and be acoustically attenuated by anti-vibration feet and stainless steel braided flexible hoses. A 35 mm supply is required, which must maintain a dynamic pressure of 1.0 bar.

Amend as required:
[1] 5-4 or 5-10
[2] 1.5 bar @ 1.5 lt/s (model 5-4)
[2] 4 bar @ 2 lt/s (model 5-10)

Dual Pump – Duty Assist
A Break Tank and Booster set with a hygienic Type AB air gap “Boost-A-Break” shall be installed – model BTAB3-5A1 - as manufactured and distributed by Arrow Valves Ltd - Tel 01442 823123 www.arrowvalves.co.uk. The unit shall have a 24 litre nominal cistern and stainless steel raised valve chamber, with a lid, screened weirs, cistern drip tray with two DN40 connections, which require an overflow pipe. The pumps shall be centrifugal with stainless steel impellors and housings. The pump speeds shall be varied by an integral inverter to provide a constant pressure. The pump controller shall feature alternate pump starting. The duty at 100% output shall be 2.0 bar2 @ 1.6 lt/s and be controlled by a pressure transducer, which is damped with a 24 litre pressure vessel. The cistern level shall be controlled automatically by two servo solenoid valves operated via stainless steel conductive electrodes and controller. A low-level pump cut-out shall be controlled by electrodes in the cistern, which shall automatically reset once the cistern is sufficiently full. The cistern shall feature a high-level alarm linked to a volt free BMS relay - model BTBMS2. The unit shall feature a stainless steel base plate and be acoustically attenuated by anti-vibration feet and stainless steel braided flexible hoses. A 35 mm supply is required, which must maintain a dynamic pressure of 1.0 bar.

Amend as required:
[1] 3-7A or 3-10A
[2] 3.0 bar (model 3-7A)
[2] 4.0 bar (model 3-10A)

Dual Pump – Duty Standby
A Break Tank and Booster set with a hygienic Type AB air gap “Boost-A-Break” shall be installed – model BTAB3-7S1 - as manufactured and distributed by Arrow Valves Ltd - Tel 01442 823123 www.arrowvalves.co.uk. The unit shall have an 18 litre cistern, with a lid, screened weirs, cistern drip tray requiring a DN40 overflow.2 The pumps shall be centrifugal with stainless steel impellors and housings. The pump speeds shall be varied by an integral inverter to provide a constant pressure. The pump controller shall feature alternate pump use. The duty at 100% output shall be 3.0 bar @ 0.9 lt/s3 and be controlled by a pressure transducer, which is damped with a 24 litre pressure vessel. The cistern level shall be controlled automatically by servo solenoid valve(s) operated via stainless steel conductive electrodes and controller. A low-level pump cut-out shall be controlled by electrodes in the cistern, which shall automatically reset once the cistern is sufficiently full. The cistern shall feature a high-level alarm linked to a volt free BMS relay - model BTBMS2. The unit shall feature a stainless steel base plate and be acoustically attenuated by anti-vibration feet and stainless steel braided flexible hoses. A 35 mm4 supply is required, which must maintain a dynamic pressure of 1.0 bar.

Amend as required:
[1] 3-10S
[1] 5-4S
[1] 5-8S
[2] The unit shall have a 24 litre nominal cistern and stainless steel raised valve chamber, with a lid, screened weirs, cistern drip tray with two DN40 connections, which require an overflow pipe. (model 5-4S or 5-8S)
[3] 4.0 bar @ 0.9 lt/s (model 3-10S)
[3] 1.5 bar @ 1.5 lt/s (model 5-4S)
[3] 3.0 bar @ 2 lt/s (model 5-8S)
[4] 22 mm (model 3-7S)
[4] 28 mm (model 3-10S or 5-4S)

 

Application

The following are Fluid Category 5 examples from the Water Regulations (Table 6.1e) -
• Hose union taps – non-domestic
• Wash-down – animals or any Fluid Category 5
• Underground or surface irrigation
• Baths in health care premises
• Sinks with hoses
• Bidet washing
• Dental equipment
• Vegetable washing
• Butchery & meat equipment
• Slaughterhouse equipment
• Laboratories
• Clothes washing machines – healthcare premises
• Dish washing machines – healthcare premises
• Applications deemed to be Category 5 by water company

 

Additional Resources

Tutorials:
• Hose Union Taps
• Filling Heating Systems
• Clothes & Dishwashing
• Washroom
• Showers, Baths & Bidets

Presentation:
• Backflow Mini Presentation
• Hose Union Taps Mini Presentation
Please see 'Required Viewers' page for assistance with viewing presentations.

Pump Curves:
• Fixed Speed (inc 4 Series)
• 3 & 5 Series Variable - Full Speed
• 3 & 5 Series Variable - Constant Pressure
• Fixed Speed (inc 4 Series), 3 & 5 Series Variable

• Picture - Boost-A-Break Installed (shown in optional GRP enclosure - BTCAB1)