01442 823 123 enquiries@arrowvalves.co.uk

DN15 Pipe Interrupter DC for Laboratory Tap

DC Pipe Interrupters provide Fluid Category 5 backsiphonage protection (vacuum on the supply). Model DC15F257 can be fitted to most standard laboratory taps that have a removable nozzle with a 1/2" BSP thread. DC Pipe Interrupters are intended for open outlet applications and must not be used for washing machines, upstream of hose union taps or any appliance that has a control valve or restriction. Negligible restriction should exist downstream - otherwise water would ultimately discharge through the vent holes.
Product Code: DC15F257
Postcode

Availability: In stock

£38.00

Additional Information

Fluid Category 5 / Booster Pumps - Max. Flow Rate No
Fluid Category 5 / Booster Pumps - Outlet Pressure No
Fluid Category 5 / Booster Pumps - Inlet Size DN15
Fluid Category 5 / Booster Pumps - Outlet Size DN15
Fluid Category 5 / Booster Pumps - Voltage No
Fluid Category 5 / Booster Pumps - Number of Pumps No
Fluid Category 5 / Booster Pumps - Cistern Size No
Fluid Category 5 / Booster Pumps - Powered No

Application

Laboratory Taps that have a removable nozzle with a 1/2" BSP thread.

Downloads & Resources

Specification Clauses

Every laboratory tap shall be fitted with a DC Pipe Interrupter, suitable for Fluid Category 5 backsiphonage protection – model DC15F257 – as manufactured by Arrow Valves Ltd – Tel 01442 823123 www.arrowvalves.co.uk. The device shall be fitted with a short unrestricted hose, which discharges at least 150 mm below the air vents of the DC device. No valves or restrictions shall be fitted downstream of the device. The body of the device shall be chrome plated with a DN15 female inlet.